One suite's air may not enter another's

Your suite's air may not reach the corridor. The corridor's air may be how your suite breathes.

You assume air moves through a building as it likes. The Code forbids one suite's air from reaching another suite or the public corridor, because of fire and smoke. But many Toronto towers ventilate their suites the other way: fresh air is pushed into the corridor and through a deliberate gap under each suite door.

Piece 23 · Design · 4 min read · By

AIR MAY NOT CROSS FROM ONE SUITE TO ANOTHER, OR INTO THE CORRIDOR public corridor suite its own supply and its own exhaust suite its own supply and its own exhaust door: gap or sweep door: gap or sweep Suite air may not go to the corridor. In many towers, corridor air is meant to come in.
01

The rule is written as a prohibition, in one sentence

You have probably assumed that air moves through a building and the corridor is part of the circuit. The Code forbids one direction. Many buildings rely on the other.

The ventilation provisions say it directly: in a residential occupancy, air from one suite shall not be circulated to any other suite or to a public corridor. That is a prohibition, and the National Building Code states its purpose: to limit the chance that fire or smoke in one suite reaches another suite or the corridor.

The exceptions are narrow and specific. A public corridor may be used as part of a supply air system serving toilet rooms, bathrooms, shower rooms and similar auxiliary spaces that open directly onto it. Everything else is closed off.

02

And the corridor may not be used as the building's duct either

The same section says a public corridor shall not be used as a portion of a supply, return or exhaust air system serving adjoining areas. A later sentence prohibits a public corridor or an exit from being used as a return-air plenum at all.

There is one thing a corridor may be used for, and it is not ventilation: it may form part of an engineered smoke control system. That is a different system with a different purpose.

In practice, many existing towers rely on the corridor anyway. A rooftop unit pushes fresh air into each corridor, the air reaches the suites through an intentional gap under the entry door, and it leaves through the bathroom and kitchen fans. Building scientists have measured these systems delivering air unevenly, some suites getting far more than others, and newer buildings are moving to a supply for each suite.

Your air may not go to the corridor. The corridor's air may come to you.

03

What that looks like at your own door

Once you know the two directions, the bottom of your door tells you which kind of building you are in.

Do this along your own corridor, without opening anything
  1. Look at the bottom of your entry door. A deliberate gap usually means the corridor is your fresh-air supply. A sweep or seal means it is not, and your suite should have a supply of its own.
  2. Hold a tissue at that gap with the bathroom fan running. If it pulls inward, the corridor is feeding your suite.
  3. Look for whether anything has been fitted above or beside the door later: a louvre, a grille, a letterbox through the door. Those are changes to a separator, and they are worth asking about.
  4. Find the grilles in the corridor ceiling or walls. In a pressurized building, the air they supply is meant to end up in the suites.
  5. Find the grilles inside your own unit: the kitchen and bathroom exhaust, and any supply. Those are your system. If your door is sealed and you find no supply of your own, ask the corporation how the suites are meant to get fresh air.
04

Where your air actually comes from and goes

Either way, a suite's air is a system with a supply and an exhaust. In a pressurized building the supply is the corridor and the exhaust is your bathroom and kitchen fans.

Which sets up the thing worth understanding if you ever renovate. Anything that changes the air balance of a unit (sealing the gap under the entry door (the usual fix for corridor smells), adding a powerful kitchen hood without make-up air) is a change to a system that was balanced. A suite that cannot draw air in will draw it from wherever it can, and the Code has a view about where that is permitted to be.

05

Why we send this

Few owners know how their suite gets its fresh air, and the answer is often under the front door. Knowing it changes how you read a corridor smell, a stuffy bedroom or a renovation plan.

So we read the record. One thing about how this city is actually put together, in enough detail that you can check it yourself and get the same answer. No figures we cannot source, no forecasts, nothing that expires in a fortnight.

More pieces like this, building records and neighbourhood data at 416spaces.com.

· Realtor® · RARE Real Estate Brokerage · 416spaces.com

Not advice. Nothing here is engineering, code or legal advice, and nothing here is a valuation or a prediction about any property or market. Whether a particular suite's ventilation was designed and is operating as required is a question about that building, and cannot be answered by this page. Any change to a suite's air balance is a matter for a qualified professional. The diagram is schematic and depicts no real building. No figure in this piece is a price.